What size sauna heater do you need?
Enter the room. You get the heater size, the circuit your electrician will run, and what each session costs.
Your sauna needs a
6 kW heater
It has 268 cu ft to heat, counting glass and bare surfaces, which takes 5.4 kW.
- 3
- 4.5
- 6
- 8
- 9
- 10.5
- 12
Electrical
| Draw at 240 Vsingle phase, hardwired, on its own circuit | 25.0 A |
|---|---|
| 125% for a continuous loadthe figure electricians size the circuit from | 31.3 A |
| Breakerwhat heater makers publish for this size | 30 A to 40 A, double-pole |
| Copper wireheavier for runs over about 50 ft | 10 AWG or 8 AWG |
Heater makers publish their own breaker and wire sizes and they differ between models. The installation manual for your heater, and your electrician, decide. What the wiring involves.
What it costs to run
| Electricity per session40 min heat-up, then 30 min in use | 5.5 kWh |
|---|---|
| Cost per sessionlikely range $0.94 to $1.07 | $0.99 |
| Cost per month3 sessions a week at $0.18 per kWh | $12.87 |
| Cost per year | $154 |
How the size was worked out
| Room volume6 × 6 × 7 ft, or 7.1 m³ | 252 cu ft |
|---|---|
| Allowance for glass and bare surfaces4 sq ft × 3.94 cu ft | + 16 cu ft |
| Volume the heater must cover7.6 m³ | 268 cu ft |
| Heater power needed1 kW for every 50 cu ft | 5.4 kW |
6 kW heater. About $0.99 a session.See the working
What this works out that a sizing chart leaves off
Glass and bare surfaces. A glass door or a tiled wall behind the heater soaks up heat. Each square foot counts as 3.94 extra cubic feet of room, which is often enough to move a sauna up a heater size.
The circuit. The heater size sets the amps, the breaker and the wire. Those decide whether your panel has room and what the electrician will charge.
The running cost. Electricity for the heat-up and the session, at the price on your own bill.
Every rule and source is on the method page.
More tools and guides
Common questions
What size heater does a 6 x 6 sauna need?
A 6 by 6 foot sauna with a 7 foot ceiling holds 252 cubic feet. With a small window in the door it needs 5.4 kW, so a 6 kW heater. Swap in an all-glass door and it needs 6.1 kW, which moves it up to 8 kW.
How do you calculate sauna heater size?
Multiply the inside length, width and ceiling height to get cubic feet. Add 3.94 cubic feet for every square foot of glass, tile, stone or concrete, because those surfaces soak up heat. Allow 1 kW for every 50 cubic feet, then choose the smallest standard heater at or above that figure.
What size breaker does a 6 kW sauna heater need?
A 6 kW heater draws 25 amps at 240 volts. Heater makers publish 30 to 40 amp double-pole breakers for this size, with 10 or 8 AWG copper wire. The installation manual for your heater decides which.
How much does it cost to run a home sauna?
A 6 kW heater uses about 5.5 kWh for a 40 minute heat-up and a 30 minute session. At the U.S. average of $0.18 per kWh that is $0.99 a session, or about $12.87 a month at three sessions a week.