Sauna electrical requirements: circuit, breaker and wire

An electric sauna heater is one of the largest loads in a house. Nearly every traditional heater above about 2 kW needs its own 240 volt circuit, hardwired, with nothing else on it. The heater size decides everything else.

Amps, breaker and wire by heater size

HeaterDraw at 240 VWith 125%BreakerCopper wire
3 kW12.5 A15.6 A20 A12 AWG
4.5 kW18.8 A23.4 A30 A10 AWG
6 kW25.0 A31.3 A30 to 40 A10 AWG or 8 AWG
8 kW33.3 A41.7 A40 to 50 A8 AWG
9 kW37.5 A46.9 A50 A8 AWG or 6 AWG
10.5 kW43.8 A54.7 A50 to 60 A6 AWG
12 kW50.0 A62.5 A70 A4 AWG

Breaker and wire columns are what heater makers publish for each size; the 12 kW row is worked out from the 125% rule.

Where the numbers come from

Amps are watts divided by volts. A 6 kW heater is 6,000 รท 240 = 25 amps.

The 125% figure is the allowance electrical codes make for a load that runs for long stretches. Electricians size the circuit from it.

Published breaker sizes vary. For a 6 kW heater one maker lists a 30 amp breaker and another lists 40. Each heater is tested and listed with the protection in its own manual, so the manual wins over any chart, including this one.

Things that change the job

Infrared cabins

Infrared saunas draw far less. One and two person cabins of about 1,400 to 1,800 watts plug into a 120 volt outlet, though a dedicated 20 amp circuit avoids tripped breakers. Larger cabins often need 240 volts.

What to give your electrician

Permits and inspection are normally required for a new 240 volt circuit in both the United States and Canada.