6 kW sauna heater

A 6 kW electric heater covers a sauna of up to about 300 cubic feet and draws 25.0 amps at 240 volts.

Room size

Largest room1 kW for every 50 cu ft300 cu ft
Comfortable up toheats faster, better outdoors in the cold270 cu ft
In metric8.5 m³

Common rooms that take this size, with a 7 foot ceiling and a small window in the door: 5 × 7 ft, 6 × 6 ft.

Breaker and wire

Draw at 240 V, single phase25.0 A
With 125% for a continuous load31.3 A
Breaker, double-poleas published by heater makers30 to 40 A
Copper wireheavier for runs over about 50 ft10 AWG or 8 AWG
Output on a 208 V supply4.5 kW

The heater is hardwired on its own circuit. Published breaker sizes differ between models of the same power, so the installation manual decides. On a 208 volt supply, found in some condos and commercial buildings, the same heater gives about three quarters of its rated heat. More on the wiring.

Running cost

A 40 minute heat-up at full power, then 30 minutes of use with the heater cycling about half the time, uses 5.5 kWh.

Electricity pricePer sessionPer month, 3 a week
$0.12 per kWh$0.66$8.58
$0.18 per kWh$0.99$12.87
$0.30 per kWh$1.65$21.45

Common questions

What size room does a 6 kW sauna heater cover?

Up to about 300 cubic feet, at 1 kW for every 50 cubic feet. It is most comfortable below 270 cubic feet. Glass and bare masonry count as extra volume.

What size breaker does a 6 kW sauna heater need?

It draws 25.0 amps at 240 volts, and 31.3 amps once the 125% allowance for a continuous load is added. Heater makers publish a 30 to 40 A double-pole breaker with 10 AWG or 8 AWG copper wire.

How much does a 6 kW sauna heater cost to run?

About 5.5 kWh for a 40 minute heat-up and a 30 minute session. That is $0.99 at $0.18 per kWh.

Check the size against your own room, glass and ceiling height.