Sauna heater sizes by room
Common rooms with a 7 foot ceiling, and what each standard heater needs from your panel.
By room size
| Room | Volume | Wood door | Door with a window | All-glass door |
|---|---|---|---|---|
| 4 × 4 ft | 112 cu ft | 3 kW | 3 kW | 4.5 kW |
| 4 × 6 ft | 168 cu ft | 4.5 kW | 4.5 kW | 4.5 kW |
| 5 × 5 ft | 175 cu ft | 4.5 kW | 4.5 kW | 6 kW |
| 5 × 7 ft | 245 cu ft | 6 kW | 6 kW | 8 kW |
| 6 × 6 ft | 252 cu ft | 6 kW | 6 kW | 8 kW |
| 6 × 7 ft | 294 cu ft | 6 kW | 8 kW | 8 kW |
| 6 × 8 ft | 336 cu ft | 8 kW | 8 kW | 8 kW |
| 7 × 7 ft | 343 cu ft | 8 kW | 8 kW | 8 kW |
| 8 × 8 ft | 448 cu ft | 9 kW | 10.5 kW | 10.5 kW |
| 8 × 10 ft | 560 cu ft | 12 kW | 12 kW | over 12 kW |
| 8 × 12 ft | 672 cu ft | over 12 kW | over 12 kW | over 12 kW |
By heater
| Heater | Covers up to | Draw at 240 V | Breaker | Copper wire |
|---|---|---|---|---|
| 3 kW | 150 cu ft | 12.5 A | 20 A | 12 AWG |
| 4.5 kW | 225 cu ft | 18.8 A | 30 A | 10 AWG |
| 6 kW | 300 cu ft | 25.0 A | 30 to 40 A | 10 AWG or 8 AWG |
| 8 kW | 400 cu ft | 33.3 A | 40 to 50 A | 8 AWG |
| 9 kW | 450 cu ft | 37.5 A | 50 A | 8 AWG or 6 AWG |
| 10.5 kW | 525 cu ft | 43.8 A | 50 to 60 A | 6 AWG |
| 12 kW | 600 cu ft | 50.0 A | 70 A | 4 AWG |
Breaker and wire sizes are what heater makers publish for each size. They differ between models, so the manual for your heater decides.