10.5 kW sauna heater
A 10.5 kW electric heater covers a sauna of up to about 525 cubic feet and draws 43.8 amps at 240 volts.
Room size
| Largest room1 kW for every 50 cu ft | 525 cu ft |
|---|---|
| Comfortable up toheats faster, better outdoors in the cold | 473 cu ft |
| In metric | 14.9 m³ |
Common rooms that take this size, with a 7 foot ceiling and a small window in the door: 8 × 8 ft.
Breaker and wire
| Draw at 240 V, single phase | 43.8 A |
|---|---|
| With 125% for a continuous load | 54.7 A |
| Breaker, double-poleas published by heater makers | 50 to 60 A |
| Copper wireheavier for runs over about 50 ft | 6 AWG |
| Output on a 208 V supply | 7.9 kW |
The heater is hardwired on its own circuit. Published breaker sizes differ between models of the same power, so the installation manual decides. On a 208 volt supply, found in some condos and commercial buildings, the same heater gives about three quarters of its rated heat. More on the wiring.
Running cost
A 40 minute heat-up at full power, then 30 minutes of use with the heater cycling about half the time, uses 9.6 kWh.
| Electricity price | Per session | Per month, 3 a week |
|---|---|---|
| $0.12 per kWh | $1.16 | $15.02 |
| $0.18 per kWh | $1.73 | $22.52 |
| $0.30 per kWh | $2.89 | $37.54 |
Common questions
What size room does a 10.5 kW sauna heater cover?
Up to about 525 cubic feet, at 1 kW for every 50 cubic feet. It is most comfortable below 473 cubic feet. Glass and bare masonry count as extra volume.
What size breaker does a 10.5 kW sauna heater need?
It draws 43.8 amps at 240 volts, and 54.7 amps once the 125% allowance for a continuous load is added. Heater makers publish a 50 to 60 A double-pole breaker with 6 AWG copper wire.
How much does a 10.5 kW sauna heater cost to run?
About 9.6 kWh for a 40 minute heat-up and a 30 minute session. That is $1.73 at $0.18 per kWh.
Check the size against your own room, glass and ceiling height.